Application Guide
Principle of Operation
- 1. Recirculation heating, automatic temperature control
- 2. Dehumidification with extract heat exchange to fresh air, auto humidity & temp. control
- 3. Manual ventilation control, summer cooling, heating off
Product Data
dripak | Dimensions LxBxH (m) |
Weight (kg) |
Lphw Heating Capacity (kW) |
Air Supply m³/s |
Max Pool Area m² |
Pool Enclosure m³ |
Moisture Extraction l/hr |
A150 | 1.4 x 1.1 x 0.6 | 151 | 32 | 0.6 | 72 | 500 | 6.2 |
A225 | 1.9 x 1.2 x 0.7 | 192 | 38 | 1.2 | 98 | 1020 | 9.7 |
A300 | 2.2 x 1.3 x 0.7 | 252 | 45 | 1.8 | 139 | 1440 | 13.6 |
A500 | 2.95 x 1.3 x 1.1 | 380 | 80 | 2.8 | 189 | 2100 | 20.7 |
A700 | 3.15 x 1.55 x 1.3 | 515 | 115 | 3.6 | 272 | 3060 | 29.9 |
A900 | 3.5 x 1.7 x 1.6 | 720 | 180 | 5.6 | 330 | 4080 | 39.6 |
A1100 | 4.2 x 2.4 x 2.4 | 1210 | 240 | 8.1 | 514 | 5100 | 61.6 |
Dimensional Notes:
A150 to A700 standard configuration, high level mounting. Side wall mounting ‘W’ configuration, transpose dimensions ‘B’ and ‘H’. A900, A1100 units are floor mounting.
Standard Rating Conditions:
28°C pool water 29°C 60%rh pool air.
Service Notes:
- A150 to A300 are 240v single phase, maximum 14 amp full load
- A500 to A1100 are 415v three phase, maximum 23 amp full load
The dripak ‘A’ system family components: Standard wall, roof dual terminal connection kits with matching silencing attenuation manufactured in colour coordinated plastic coated galvanised steel sheet.
For other dehumidification applications, please contact us directly.